PROTECT D. 10000
As mentioned, the connection for the external battery pack(s) takes place at
the rear of the unit. Opening the front panel(s) is not required here.
Next, start with the contact for the first external unit. Remove the battery
connector cover from the back side of the UPS (see No.17 on page 28). Connect
the connecting cable affixed to the external battery pack from now on with the
UPS, according to the accompanying illustration. Insert the plug firmly and fully in
the reverse polarity protected battery connection jacks.
The next step pertains to the enclosed data cable with the small transparent RJ11
connectors. It is used for automatic detection of the battery unit(s). Connect the
UPS in turn with the first battery unit according to the illustration.
Repeat the above mentioned steps for adding additional external battery units.
In this case the connection of the next battery takes place on the previous one
and so on.