APC 1400XLT Power Supply User Manual


 
29
12. Specifications
1400 VA 2200 VA 3000 VA
Acceptable input voltage 0 - 325 VAC
Input voltage (on-line operation)* 160-253 VAC
208 volt output range* 176-229 VAC
120 volt output range*
with 400 VA load
with no load
95-130 VAC
100-135 VAC
Nominal input frequency 50 or 60 Hz, autosensing
Input Protection Resettable circuit breaker
Frequency limits (on-line operation) 50 or 60 Hz, ±5%
Transfer time 2 ms typical, 4.5 ms maximum
Maximum load, Total 1400 VA/950 W 2200 VA/1600 W 3000 VA/2250 W
Maximum load, 120V auxilliary 400 VA/400 W
On-battery output voltage 208 VAC
On-battery frequency
50 or 60 Hz, ±0.1 Hz; unless synchronized to utility during
brownout.
On-battery waveshape Low-distortion sine wave
Overload protection (on-battery)
Overcurrent and short-circuit protected, latching
shutdown on overload.
Overload protection (on-line) 2 pole, 20 Amp UL certified input circuit breaker
Overload protection (120VAC auxiliary)
Transformer and output protected by resettable thermal
circuit breaker (on-line and on-battery)
Surge energy rating (one time, 10/1000 µs
waveform)
1120 J
Surge current capability (one time, 8/20 µs
waveform)
6500 A maximum
Surge response time
0 ns (instantaneous) normal mode;
<5 ns common mode
Surge voltage let-through (percentage of
applied ANSI C62.41 Cat. A ±6 kV test
waveform)
0.30%
Noise Filter
Normal and common mode EMI/RFI suppression, 100
kHz to 10 MHz
* settings may be changed via optional software