3000 VA Models
Typical On-Battery Run Time Versus Load, in Minutes
Load Internal Battery 1 Battery Pack
100 VA 228 491
150 VA 183 394
200 VA 152 328
300 VA 110 245
400 VA 84 193
500 VA 67 157
600 VA 54 131
800 VA 36 96
1000 VA 26 73
1200 VA 20 58
1400 VA 16 46
1600 VA 13 37
2000 VA 10 26
2200 VA 8 22
2500 VA 7 18
3000 VA 5 13