APC 1400XLT Power Supply User Manual


 
33
14. User Configuration Items
Note: Setting these items requires optional software or hardware.
Function
Factory
Default
User Selectable
Choices
Description
Automatic Self-Test
Every 14
days (336
hours)
Every 7 days (168
hours), On Startup
Only, No Self-Test
Sets the interval at which the UPS will
execute a self-test.
UPS ID UPS_IDEN
Up to eight
characters to define
the UPS.
Use this field to uniquely identify the
UPS for network management
purposes.
Date of Last Battery
Replacement
Manufactur
Date
Date of Battery
Replacement
Reset this date on battery
replacement.
Minimum Capacity
Before Return from
Shutdown
0 percent 15, 50, or 90 percent
The UPS will charge its batteries to
the specified percentage before return
from a shutdown.
Sensitivity Normal Reduced, Low
Set lower than normal sensitivity to
avoid lowered battery capacity and
service life in situations where the
load can tolerate minor power
disturbances.
Duration of Low
Battery Warning
2 minutes 5, 7, or 10 minutes
Sets the time before shutdown at
which the UPS issues a low battery
warning. Set higher than the default
only if the OS needs the time for
graceful shutdown.
Alarm Delay After
Line Fail
5 second
delay
30 second delay, At
Low Battery
Condition, No Alarm
To avoid alarms for minor power
glitches, set the alarm delay.
Shutdown Delay 20 seconds
180, 300, or 600
seconds
Sets the interval between when the
UPS receives a shutdown command
and when shutdown occurs.
Synchronized
Turn-on Delay
0 seconds 60, 180, 300 seconds
To avoid branch circuit overload, the
UPS will wait the specified time after
the return of utility power before
turn-on.
High Transfer Point 253 Vac 264, 271, 280 Vac
Low Transfer Point 196 Vac 188, 204, 208 Vac