Minimum Breaker Settings
800% overload
bypass
operation
150% overload
normal/battery
operation
125% overload
normal/battery
operation
Continuously
Duration 500 ms 60 s 10 min
Mains input
-
1
- -
34 A
Static bypass
input
223 A
- -
31 A
10 kVA
UPS output 223 A 42 A 35 A 31 A
Mains input
-
1
- -
51 A
Static bypass
input
333 A
- -
46 A
15 kVA
UPS output 333 A 63 A 52 A 46 A
Mains input
-
1
- -
68 A
Static bypass
input
444 A
- -
62 A
20 kVA
UPS output 444 A 84 A 70 A 62 A
Mains input
-
1
- -
99 A
Static bypass
input
667 A
- -
92 A
30 kVA
UPS output 667 A 125 A 105 A 92 A
1
For single mains systems, use the higher value of mains and static bypass
990-1957C-001
MGE™ Galaxy™ 3500 10-30 kVA 208/220 V Single and Parallel Installation