APC G35T10KF1B2S Power Supply User Manual


 
Specications
WARNING: The UPS must be supplied from a 208/120 V or 220/127 V 4W + GND
60 HZ source.
AC Input Specications
10 kVA 15 kVA 20 kVA 30 kVA
208 V 220 V 208 V 220 V 208 V 220 V 208 V 220 V
Connection type 4-wire (3PH + N + G)
Input frequency
(Hz)
40-70
I thd < 5% at full load
Nom input current
(A)
24.3 23.0 36.6 34.6 48.6 45.8 73.2 69.0
Max input current
(A)
26.7 25.2 40.2 38.0 53.0 50.1 80.1 75.8
Input current
limitation (A)
32.8 32.8 49.5 49.5 65.2 65.2 98.8 98.8
Input power factor
correction
> 0.98 at load > 50%
Maximum Short
Circuit Withstand
(kA)
30
AC Bypass Input Specications
10 kVA 15 kVA 20 kVA 30 kVA
208 V 220 V 208 V 220 V 208 V 220 V 208 V 220 V
Connection type 4-wire (3PH + N + G)
Input frequency
(Hz)
50 +/- 10 or 60 +/- 10
Nom input current
(A)
27.8 26.2 41.6 39.4
55.5
52.5 83.3 78.7
2
MGE™ Galaxy™ 3500 10-30 kVA 208/220 V Single and Parallel Installation
990-1957C-001