WARNING: The UPS must be supplied from a 208/120 V or 220/127 V 4W + GND
60 HZ source.
AC Input Specications
10 kVA 15 kVA 20 kVA 30 kVA
208 V 220 V 208 V 220 V 208 V 220 V 208 V 220 V
Connection type 4-wire (3PH + N + G)
Input frequency
(Hz)
40-70
I thd < 5% at full load
Nom input current
(A)
24.3 23.0 36.6 34.6 48.6 45.8 73.2 69.0
Max input current
(A)
26.7 25.2 40.2 38.0 53.0 50.1 80.1 75.8
Input current
limitation (A)
32.8 32.8 49.5 49.5 65.2 65.2 98.8 98.8
Input power factor
correction
> 0.98 at load > 50%
Maximum Short
Circuit Withstand
(kA)
30
AC Bypass Input Specications
10 kVA 15 kVA 20 kVA 30 kVA
208 V 220 V 208 V 220 V 208 V 220 V 208 V 220 V
Connection type 4-wire (3PH + N + G)
Input frequency
(Hz)
50 +/- 10 or 60 +/- 10
Nom input current
(A)
27.8 26.2 41.6 39.4
55.5
52.5 83.3 78.7
2
MGE™ Galaxy™ 3500 10-30 kVA 208/220 V Single and Parallel Installation