Emerson Series 600T Power Supply User Manual


 
Installation Drawings
139
Figure 147 Wiring specifications, Liebert FS and Liebert Series 610
Wire
No.
Terminal
Designation
Signal
Name
Maximum
Voltage
Maximum
Current Color
Wire Size
& Type
Maximum
Length
Remarks
From To
Liebert Series 610 UPS - Cable Group #16 (Flywheel CB IFM) From I1 in UPS Module to TB1 on Liebert FS Module
901 I1-TB1-1 TB1-1 Trip Signal (+) +24 VDC 100mA
1/C #16 (2.5 mm
2
)
Stranded
500 Ft
(150 M
902 I1-TB1-2 TB1-2 Trip Signal (-) -24 VDC 100mA
903 I1-TB1-7 TB1-7 Aux Comm 24 VDC 100mA
904 I1-TB1-8 TB1-8 Aux N.O. 24 VDC 100mA
Liebert Series 610 UPS - Cable Group #116 Flywheel Aux Power, Customer-Provided to Liebert FS TB1 on Fused
Disconnect
914 FBO TB1-1 Line 120VAC 3.5A
1/C #16 (2.5 mm
2
)
Stranded
500 Ft
(150m)
UPS-
Protected
Auxiliary
Power
Control
915 FBO TB1-2 Neutral 120VAC 3.5A
916 FBO TB1-3 GND 120VAC 3.5A
1. Each cable group must be run in a separate, grounded, rigid metal conduit to prevent control signal interference.
2. Refer to UPS module/Liebert FS control connection diagram for location of wiring connections.
3. All external wires furnished by others.
4. N.O. = Normally Open; N.C. = Normally Closed; Comm = common; F.B.O. = Furnished By Others, GND = ground
5. All wiring must be in accordance with national and local electrical codes.
Dwg. No. Control_WL_S610_Liebert-FS Rev. 01