Emerson Series 600T Power Supply User Manual


 
Troubleshooting
81
8.3 Faults
A Fault is defined as an undesirable system operating condition that could cause further damage to
the system or potentially drop the load. Once detected, Faults may trigger an appropriate emergency
action such as shutting the unit down. Most Fault conditions are automatically taken care of by the
Liebert FS control system and require no Operator intervention. A few Fault conditions may be
resolved only through operator intervention or service by a Liebert technician.
A Fault condition must be valid for a certain amount of time before it is recognized as an active Fault.
This prevents spurious signals from causing false Fault detection and unnecessary state changes.
Figure 93 shows the appearance of an active Fault on the main screen.
Figure 94 Fault screen descriptions
While in Fault condition, normal operation of the unit is suspended, the operation of the Power Con-
version Module is paused, and the unit transitions into FAULT Mode, where it waits for one of the fol-
lowing to occur:
1. The condition to clear the fault [AUTO CLEAR]
2. The unit to automatically transition in SHUTDOWN Mode [AUTO SHUTDOWN]
3. Operator action [OPERATOR CLEAR].
The Fault condition is indicated by the System Mode displaying “FAULT” in the Control Panel win-
dow.
If there are multiple Fault conditions present, the F5 “More Info” key will be enabled in the Control
Panel window. If pressed, information related to the specific Faults will be displayed in the Control
Panel window (see Figures 54 through 56). If there are multiple faults they will both be displayed by
pressing the F5 “MORE” button.
In many cases, when FAULT Mode is entered, the Fault may be cleared by pressing the F3 “CLEAR
FAULT” button on the Control Panel or utilizing the VIB option - if enabled - to send a “CLEAR
FAULT” signal to the system. In order to “CLEAR FAULT” the operator must be in proper security
access level; User or above. Table 16 describes the fault labels, meanings and possible causes for the
MODE:
STATUS:
D V U C
RPM:
SOC:
SOC:
BUS:
PWR:
48351
75.4%
538V
0.0kW
FAULT
2 FAULTS
CLEAR MORE MENU
Liebert FS
More information
Button (F5)
Fault Status Message
Fault Clear Button (F3)
Bus Power