Table 2-2 Server Dimensions and Values (continued)
ValuesDimension
0.2 m
2
(2.1 sq. ft.)Pedestal footprint
2URack units
Grounding
The site building shall provide a safety ground or protective earth for each AC service entrance
to all cabinets.
Install a PE (protective earthing) conductor that is identical in size, insulation material, and
thickness to the branch-circuit supply conductors. The PE conductor must be green with yellow
stripes. The earthing conductor is to be connected from the unit to the building installation earth
or, if supplied by a separately derived system, at the supply transformer or motor-generator set
grounding point.
Electrical Specifications
This section provides electrical specifications for the server.
AC Power Cables
Table 2-3 lists the power cables available for use with the HP 9000 rp3410 and rp3440 servers.
Table 2-3 Power Cables
CountryDescriptionPart Number
South AfricaPower Cord C15/S Africa 2.5m black CA ASSY 9178120-5341
United Kingdom
Hong Kong
Singapore
Power Cord C13/BS-1363 2.3m black CA ASSY 9008120-1351
AustraliaPower Cord C13/AS-3112 2.0m gray CA ASSY 9018120-1369
EuropePower Cord C13/CEE 7 2.0m black CA ASSY 9028120-1689
SwitzerlandPower Cord C13/SEV 12 2.0m black CA ASSY 9068120-2104
DenmarkPower Cord OPT-912 3-COND 2.25-M-LG 9128120-6814
North America (250#V)
Japan
Power Cord C13/6-15P 0.0m black CA ASSY 904 / 9188120-0698
IsraelPower Cord OPT-919 3-COND 2.3-M-LG 9198120-6800
ArgentinaPower Cord C15/CEI 23-16 2.5m black CA ASSY 9208120-8390
ChilePower Cord C15/CEI 23-16 2.5m black CA ASSY 9218120-8389
ChinaPower Cord C13/GB-1002 2.236m gray CA ASSY 9228120-8376
South AmericaPower Cord OPT-927 3-COND 2.3-M-LG FLNT 9278121-0668
AllC13/C14 Jumper cord8120-6514
Circuit Breaker
The marked electrical for the server is 7.2 amps. The recommended circuit breaker size is 12 amps
per line cord (two maximum) for North America. For countries outside North America, consult
the local electrical authority that has jurisdiction for the recommended circuit breaker size.
42 System Specifications