Overcurrent protection—The appliance is designed for an AC line voltage
source with up to 20 amperes of overcurrent protection. If the power system for
the equipment rack is installed on a branch circuit with more than 20 amperes of
protection, you must provide supplemental protection for the appliance. If more
than one appliance is installed in the rack, the power source for each appliance
must be from a separate branch circuit.
Temperature—The operating temperature of the appliance, when installed in an
equipment rack, must not go below 5 °C (41°F) or rise above 35 °C (95 °F).
Extreme fluctuations in temperature can cause a variety of appliance problems.
Ventilation—The equipment rack must provide sufficient airflow to the front of
the appliance to maintain proper cooling. There must be sufficient ventilation to
exhaust at least 1,500 BTU per hour for each appliance. The rack selected and
the ventilation provided must be suitable to the environment in which the
appliance will be used.
BIOS error codes
The following is a list of BIOS error codes with their corresponding descriptions.
BIOS error codes appear on the appliance's LCD screen.
BIOS error code Description
0100h Timer Channel 2 Error
0101h Master Interrupt Controller
0102h Slave Interrupt Controller
0103h CMOS Battery Failure
0104h CMOS Options Not Set
0105h CMOS Checksum Failure
0106h CMOS Display Error
0107h Insert Key Pressed
0108h Keyboard Locked Message
0109h Keyboard Stuck Key Message
010Ah Keyboard Interface Error
010Bh System Memory Size Error
010Eh External Cache Failure
0110h Floppy Controller Error