2.1.2 Identification Setup Screen
The Identification Setup screen is accessed from the Enter Setup screen when the password is entered. For a
Single-Module the Identification Setup allows the User to modify the naming conventions for the UPS’s, circuit
breakers, and inputs of the unit. For Multi-Module system the Identification Setup and System Configuration
screens allow the User to modify the naming conventions. See Figure 2-2 for the Identification Setup for a Single-
Module, and Figure 2-3 for a Multi-Module. See Figure 2-4 for the System Configuration screen for the
Multi-Module.
The following is a description of the screen buttons.
Default names
Show CB’s/System CB Configuration
Battery Temp. Sensor present
Show battery Backup Time
Alarm Pop-up Screen
Select if UPS is a 225, 300, 375 or 500KVA
Change Password
WARNING: A Password for the Control Panel and clearing the alarm his-
tory is required. User should note password and keep in a
secure location.
Control Panel
CAUTION: Use Caution in this menu as some settings can have adverse
affects on the GCC operation.
UPS’s Present
9
8
7
6
5
4
3
2
1
GCC Setup
Graphical Command Center
page 2 — 2
These are the text fields that appear on the mimic diagram. Change
these text fields by double-clicking inside the box, and the keypad
will appear allowing you to enter text. The default name (UPS Name
= UPS 1) can be changed by double-clicking in the first text field and
entering the UPS name. For instructions to use the keypad, see
section 1.4 Keypad.
Enable or disable circuit breakers in the system configuration. Green
is enabled, and gray is disabled. If disabled, the breaker will not be
shown in the mimic diagram.
Enable battery temperature monitoring (if that option was installed).
Green is enabled, and gray is disabled.
Shows the UPS battery backup time. The UPS needs to have bat-
tery parameters programmed in order for this to work correctly.
Refer to the UPS Manual, or contact Customer Service Support at
1-800-438-7373
.
When enabled this button will set the Alarm/Event Present screen
to open every time there is an unacknowledged alarm. Once
enabled, the Alarm/Event Present screen will not close until all
alarms/events are acknowledged. This may also be enabled in the
Alarm/Event Present screen.
Disabling will filter alarms specific to 800 kVA class UPS’s.
Selecting this menu button will open the Change Password screen.
Refer to section 2.1.3 Change Password for the procedure.
Selecting this menu button will open the Control Panel screen.
Refer to section 2.1.4 Control Panel to change the settings.
Selects number of UPS’s in a Multi-Module System. Green is
enabled and gray is disabled.