MGE UPS Systems UPS Power Supply User Manual


 
The event list is for a Single-Module UPS. For a Multi-Module System, the UPS module number (from 1 to 6), with
the event will be displayed.
Events - UPS Modules
Module 1 Low Battery Shutdown Module 1 UPS Off-Line
Module 1 Battery Charging Module 1 UPS On-Line
Module 1 Battery Current Limiting activated Module 1 Inverter Output Switch Open
Module 1 Battery Equalization activated Module 1 Free Running Frequency activated
Module 1 Gradual Rec/Charger Shutdown activated Module 1 Xfer Ut. 2w/inter. prohibited activated
Module 1 2nd Step Input Current Limit activated Module 1 Transfer Lockout activated
Module 1 Forced Inverter Shutdown
5.3 Alarm/Event Present Screen
The Alarm/Event Present screen lists all active alarms and events occurring in present time. Refer to Figure 5-1
for the screen selections.
Ack all Alarms Acknowledges all alarms/events. Adds the date and time stamp of acknowl-
edgement, and changes the line color to green.
History Alarms Opens the Alarm/Event History screen. When an alarm/event is acknowl-
edged, it disappears from the present log and enters into the history log.
Active/Unack Alarms Shows how many alarms are active and unacknowledged.
Ack this alarm only Acknowledges one alarm/event at a time, in the single-alarm acknowledge
window. Use the up and down arrows for selection.
Up/Down Arrows Scrolls through the list of alarms/events.
Alarm/Event List Shows a list of all present alarms/events with activation date/time, message,
date/time of acknowledgement and date/time when returned to normal. Line
colors are as follows:
Red Activated (Unacknowledged)
Green Acknowledged
Blue Returned to Normal
Alarm Pop-up Screen If selected, the Alarm/Event Present screen automatically opens when an
unacknowledged alarm occurs. Once enabled, the Alarm/Event Present
screen will not close until all alarms/events are acknowledged.
Alarm/Event Filter User can filter alarms and events to be viewed as follows: alarms only, events
only, or alarms and events.
8
7
6
5
4
3
2
1
GCC Alarms
Graphical Command Center
page 5 —2