Omron CP1E-E@@D@-@ Computer Hardware User Manual


 
2 Instructions
2-248
CP1E CPU Unit Instructions Reference Manual(W483)
Converting to ASCII Text in Scientific Notation
When CIO 0.00 is ON in the following example, FSTR(448) converts the floating-point data in D1 and
D0 to scientific-notation ASCII text and writes the ASCII text to the destination words beginning with
D100. The contents of the control words (D10 to D12) specify the details on the data format (scientific
notation, 11 characters total, 3 fractional digits).
20(Space)
2E(.)
37(7)
45(E)
30(0)
00
1010100001110010
0011111010100111
0.00
15 0
D0
D1
0001(Hex)
000B(Hex)
0003(Hex)
D10
D11
D12
0.327457
20(Space)
33(3)
32(2)
35(5)
2D(-)
31(1)
D100
D101
D102
D103
D104
D105
3.27457E-01
FSTR
D0
D10
D100
Conversion
Storage
conditions
Scientific notation
Total characters = 11 characters
Fractional digits = 3 digits (characters)
Total number of characters
Spaces
Fractional part
Rounded off