870 USE 101 00 V.3
Reserving and Monitoring a Battery Coil
Introduction Since the Option Adapter does not have an LED to indicate when the battery is low,
we recommend that you reserve a 0
x
reference to monitor the health of the battery.
This section describes how to reserve and monitor a battery coil, using the
Configuration Overview editor in Modsoft 2.6.
Reserving a
Battery Coil
To reserve a battery coil, perform the steps in the following table.
Continued on next page
Step Action
1 From the Overview menu, select Specials.
Result: The cursor moves into the Battery Coil field on the Configuration
Overview screen.
2 Enter a coil number in the range of available 0
xxxx
references.
Example: If you have set the range of 0
x
’s at 000001...001536, you might want to
enter the reference value of the last coil–1536.
3 Push <Enter>.