Schneider Electric Processor Adapter Network Card User Manual


 
Configuring an M1 CPU with Modsoft
214
870 USE 101 00 V.3
Changing the Baud Rate
Overview Each port can be configured for a baud in the range 50...19,200. Sixteen valid
bauds are user-selectable. The factory-set default is 9600 baud.
Procedure To change the baud parameter, perform the steps in the following table.
Note: If you use a baud rate lower than 4800, you should adjust the default
delay parameter. See
Changing the Delay
on page 216.
Step Action
1 Place the cursor on the current Baud entry for the Modbus port you want to enter.
Push <Enter>.
Result: A popup window appears in the top left corner of the screen displaying 16
baud values:
2 Use an arrow key to toggle the cursor onto the desired Baud selection in the popup
window, then push <Enter>.
Result: The Port editor screen is updated with the Baud number you have specified,
and the cursor moves to the Head-Slot column.