Toshiba ASD-G9ETH Network Card User Manual


 
62
ICC
Point-to-point class 1 connected messages will be produced targeting the
IP address of the device that instantiated the connection, port 0x08AE (port
2222).
If a class 1 connection’s consuming half (OT) times out, then the
producing half (TO) will also time-out and will stop producing.
If a class 1 or class 3 connection timeout occurs, the driver will trigger a
timeout event as described in section 10.7.4.
13.2.2 ControlLogix Examples: Setup
This section will demonstrate how to initially setup a ControlLogix PLC (such as
a 1756-L61) coupled with a 1756-ENBT communications bridge (adjust this
procedure according to your specific equipment). Later sections will provide
specific read/write examples using this configuration with I/O or explicit
messaging.
1) Run RSLogix 5000, and create a new configuration.
2) To add a 1756-ENET/B to your I/O configuration, first switch to offline
mode.
3) Right click on the I/O Configuration node in the controller organizer view
and choose “New Module…”
4) The “Select Module” window will open.
5) Under “Communications”, select “1756-ENET/B”, and click OK. Refer to
Figure 58.
Figure 58: Adding a New Module