94
ICC
Binary Output Object Instance Summary
Instance
ID
Object Name Description
Active/
Inactive Text
BO1 RUN_STOP_CMD Run/stop command run/stop
BO2 FWD_REV_SEL
Forward/reverse
command
reverse/forward
BO3 EMERGENCY_OFF
Emergency off
command
emergency off/
no action
BO4 FAULT_RESET Fault reset command reset/no action
BO5 FEEDBACK_CTRL_SEL
Feedback enable/
disable selection
enable/disable
BO6 FREQ_PRIORITY Frequency priority on/off
BO7 COMMAND_PRIORITY Command priority on/off
BO8 DATA_OUT1_TERMINAL
Output terminal
“selected data out 1”
on/off
BO9 DATA_OUT2_TERMINAL
Output terminal
“selected data out 2”
on/off
BO10 DATA_OUT3_TERMINAL
Output terminal
“selected data out 3”
on/off
Analog Input Object Instance Summary
Instance ID Object Name Description Units
AI1 OUTPUT_FREQ Output frequency Hz
AI2 LOAD_CURRENT Output current Percent
AI3 OUTPUT_VOLTAGE Output voltage Percent
AI4 INPUT_POWER_CONSUME Input power KW
AI5 RR_ANALOG_INPUT RR/S4 input Percent
AI6 VI_II_ANALOG_INPUT VI/II input Percent
AI7 RX_ANALOG_INPUT RX input Percent
AI8 TRIP_CODE Trip code information None
Analog Output Object Instance Summary
Instance ID Object Name Description Units
AO1 FREQ_CMD_REG Frequency command Hz
AO2 FM_ANALOG OUTPUT FM output value None
AO3 AM_ANALOG OUTPUT AM output value None