Toshiba ASD-G9ETH Network Card User Manual


 
96
ICC
BO4...... Resets the drive when it is faulted. ASD parameter FA06, bit#13.
BO5...... Enables or disables process (PID) feedback control. Note that this
object does not activate (turn on) feedback control. It only enables or
disables feedback control once it has already been activated. ASD
parameter FA06, bit#5.
BO6...... Communication interface frequency priority selection. Allows the
frequency command from the interface card to be used by the drive
without having to set the Frequency Mode parameter. Refer to the
Toshiba documentation regarding "Command Mode and Frequency
Mode Control" for detailed information pertaining to the frequency
source hierarchy and the use of overrides. ASD parameter FA06,
bit#14.
BO7...... Communication interface command priority selection. Allows
commands (BO1, BO2, and BO5) from the interface card to be used
by the drive without having to explicitly set the Command Mode
parameter. Refer to the Toshiba documentation regarding "Command
Mode and Frequency Mode Control" for detailed information pertaining
to the command source hierarchy and the use of overrides. ASD
parameter FA06, bit#5.
BO8...... Output terminal data out 1. Any programmable output terminals that
are configured to output “specified data output 1” will follow the value
of this BO. ASD parameter FA50, bit#0.
BO9...... Output terminal data out 2. Any programmable output terminals that
are configured to output “specified data output 2” will follow the value
of this BO. ASD parameter FA50, bit#1.
BO10.... Output terminal data out 3. Any programmable output terminals that
are configured to output “specified data output 3” will follow the value
of this BO. ASD parameter FA50, bit#2.
Analog Input Objects
AI1........ Output frequency in 0.01Hz units. ASD parameter FD00.
AI2........ Load current in 0.01% units (10000=100.00%=drive's rated current).
ASD parameter FE03.
AI3........ Output voltage in 0.01% units (10000=100.00%=drive's rated voltage).
ASD parameter FE05.
AI4........ Input power consumption (drive+motor) in 0.01kW units. ASD
parameter FE29.
AI5........ Indicates the signal level currently being applied to the ASD's RR
analog input terminal. This can be used to monitor such items as
feedback sensor outputs and other process variables. Expressed in
0.01% units (10000=100.00%=input rated value). ASD parameter
FE35.