Watlow Electric EZ-ZONE PM Network Card User Manual


 
Ó
Warning:
Use National Electric (NEC)
or other country-specific
standard wiring and safety
practices when wiring and
connecting this controller to
a power source and to elec-
trical sensors or peripheral
devices. Failure to do so may
result in damage to equip-
ment and property, and/or
injury or loss of life.
Note:
Maximum wire size termina-
tion and torque rating:
• 0.0507 to 3.30 mm
2
(30 to
12 AWG) single-wire termi-
nation or two 1.31 mm
2
(16
AWG)
• 0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be
labeled differently, depend-
ing on the model number.
Note:
To prevent damage to the
controller, do not connect
wires to unused terminals.
Note:
Maintain electrical isolation
between analog input 1, digi-
tal input-outputs, switched
dc/open collector outputs and
process outputs to prevent
ground loops.
Note:
The control output common
terminal and the digital com-
mon terminal are referenced
to different voltages and
must remain isolated.
Watlow EZ-ZONE
®
PM Integrated Controller 18 Chapter 2 Install and Wire
Output 1 Solid-state Relay, Form A
normally open
common
L1
K1
L2
K2
T1
S1
R1
Slot A
• 0.5 A at 20 to 264VÅ (ac) maxi-
mum resistive load
• 20 VA 120/240VÅ (ac) pilot duty
• opto-isolated, without contact
suppression
• maximum off state leakage of
105 microamperes
• output does not supply power
• Do not use on dc loads.
• See Quencharc note.
PM6 _ _ K _-_ _ _ _ A _ _
Internal Circuitry
common
normally
open
Solid-state Relay
L1
K1
Output 2 Switched DC
dc+
dc-
L1
K1
J1
W2
Y2
T1
S1
R1
Slot A
• 10 mA DC maximum supply
current
• short circuit limited to <50 mA
• 22 to 32VÎ (dc) open circuit
voltage
• use dc- and dc+ to drive exter-
nal solid-state relay
• DIN-A-MITE compatible
• single-pole: up to 2 in series,
none in parallel
PM6 _ _ _ C-_ _ _ _ A _ _
Internal
Circuitry
dc-
dc+
Load
Switched DC
-
+
W2
Y2
Output 2 No-arc Relay, Form A
common
normally open
L1
K1
J1
L2
K2
T1
S1
R1
Slot A
• 15 A at 85 to 264VÅ (ac) resis-
tive load only
• 2,000,000 cycle rating for no-arc
circuit (preliminary)
• 100 mA minimum load
• 2 mA maximum off state leakage
• Do not use on dc loads.
• Output does not supply power.
PM6 _ _ _ H-_ _ _ _ A _ _
Output 2 Mechanical Relay, Form A
common
normally open
L1
K1
J1
L2
K2
T1
S1
R1
Slot A
• 5 A at 240VÅ (ac) or 30VÎ (dc)
maximum resistive load
• 20 mV at 24V minimum load
• 125 VA pilot duty @ 120/240VÅ
(ac), 25 VA at 24VÅ (ac)
• 100,000 cycles at rated load
• Output does not supply power.
• for use with ac or dc
See Quencharc note.
PM6 _ _ _ J-_ _ _ _ A _ _
Internal
Circuitry
common
normally
open
Mechanical
Relay
L2
K2
Quencharc Note:
Switching pilot duty inductive
loads (relay coils, solenoids,
etc.) with the mechanical
relay, solid state relay or
open collector output options
requires use of an R.C. sup-
pressor.