Watlow EZ-ZONE
®
PM Integrated Controller • 70 • Appendix
Solid-State Relay
• 0.5 A @ 24 to 264VÅ (ac) maximum, opto-isolated, without con-
tact suppression; maximum off-state leakage current: 105 micro-
amperes
Electromechanical Relay, Form A
• 5 A, 24 to 240VÅ (ac) or 30VÎ (dc) maximum, resistive load,
100,000 cycles at rated load, 125 VA pilot duty
• Requires a minimum load of 20 mA @ 24V
Electromechanical Relay, Form C
• 5 A, 24 to 240VÅ (ac) or 30VÎ (dc) maximum, resistive load,
100,000 cycles at rated load, 125 VA pilot duty
• Requires a minimum load of 20 mA @ 24V
No-arc Relay Form A
• 15 A, 85 to 264VÅ (ac), no VÎ (dc), resistive load, 2 million cycles
at rated load (preliminary), maximum off-state leakage current:
2 mA
Process
• Universal process/Retransmit, outputs range selectable, 0 to 10
VÎ (dc) into minimum 1,000 Ω load, 0 to 20 mA into maximum
800 Ω load
Operator Interface
• Dual 4-digit, 7-segment LED displays
• Advance, infinity, up and down keys plus an EZ Key program-
mable function key
• Typical display update rate 1Hz
• Agency approved to IP66/NEMA 4X
Dimensions
Size Behind
Panel
(max.)
Width Height Display Height
1/16 101.6 mm
(4.00 in)
53.3 mm
(2.10 in)
53.3 mm
(2.10 in)
up: 10.80 mm (0.425 in)
low: 6.98 mm (0.275 in)
Weight
• Controller: 200 g (7.1 oz.)
• User manual: 167.26 g (5.9 oz)
Modbus® is a trademark of AEG Schneider Automation Inc.
EtherNet/IP™ is a trademark of ControlNet International Ltd. used
under license by Open DeviceNet Vendor Association, Inc. (ODVA).
UL® is a registered trademark of Underwriters Laboratories Inc.
DeviceNet™ is a trademark of Open DeviceNet Vendors Associatlon.
Note: These specifications are subject to change without prior
notice.