American Power Conversion PD80KF6FK1-M Power Supply User Manual


 
Overview
6 80kW InfraStruXure PDU—Operation and Configuration
PDU front view (exterior)
PDU wide shielding
troughs—The PDU shielding
troughs accommodate the
power cables exiting the roof of
the PDU.
Power Cables—These power
cables feed equipment racks;
they are fed through knockout
panels on the top (or bottom) of
the PDU. The power cables
consist of five wires: three
phases, one neutral, and one
ground. The number of power
cables installed in the PDU
depends on your system
configuration. Each power
cable has a NEMA L21-20
outlet, which accepts a variety
of APC InfraStruXure
accessories, including Rack
PDUs and the Rack ATS.
Sub-feed power cables—These power cables are an option for feeding RDPs; they are fed
through knockout panels on the top (or bottom) of the PDU. The power cables consist of five
wires: three phases, one neutral, and one ground. You can have up to four sub-feed power
cables. If you ordered this option, each power cable has an IEC 309 outlet, which connects to
another sub-feed power cable fed from the RDP with an IEC 309 plug.
Display interface—The display interface is attached to the name plate on the front door of the
enclosure. It has an LCD, five-button interface, basic status lights, and a beeper.
Lock-out bracket—The bracket allows for a padlock to be applied to the door to lock access
to the PDU switches and breakers.
Cable access holes—Both side panels on the PDU have cable access holes for Symmetra PX
UPS input and output wiring. During installation, the APC Field Service Engineer exchanges
side panels between the PDU and the Symmetra PX UPS so that the adjacent sides of the two
units have panels with cable access holes.
Leveling feet—The feet adjust for leveling the enclosure. All enclosures must be level before
installation of the system begins.