System Operation
38 80kW InfraStruXure PDU—Operation and Configuration
3. Set the XR Battery Enclosure DC Disconnect
circuit breaker to the OFF position.
4. Pull out all battery units in the XR Battery
Enclosures to the red battery disconnect line.
5. Set the Main Input switch (A), and, if
applicable, the Q10 Bypass Input switch (B),
and Cross Tie Output or MCCB Subfeed
circuit breaker (X) on the PDU to the OFF
position.
6. Set the Q1, Q2, and Q3 circuit breakers on the
PDU to the OFF position.
7. Set the upstream main input, and, if applicable,
the bypass input and utility circuit breaker to the
OFF or Locked Out position.
A
B