80kW InfraStruXure PDU—Operation and Configuration 67
Specifications
80 kW InfraStruXure PDU
Performance
Transformer Efficiency (if installed) 97%
System Full Load Output Rating 80kW
System Monitoring
Of Current Distribution branch monitoring (optional), subfeed
Of Voltage AC main input, bypass input, output at distribution panels,
output of fuses
Of Bypass Bypass breaker positions, bypass lamp cue/feedback
Switches/ Breakers Status Bypass breaker positions, input switch positions, cross tie
output switch position
Transformer Temperature Sensor 180°C (triggers a warning through the PDU monitoring unit)
Branch Current Monitoring
Parameters Maximum current (RMS): 95A
Maximum current (peak): 135A
Maximum crest factor: 3
Minimum current: 0.5A
Measurement accuracy: ± 0.5A or 5% of reading
(whichever is greater)
Maximum wire size: 0.35in (8.89mm)
Electrical PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M
Input
Nominal Voltage 208V Delta 480V Delta 600 V Delta
Nominal Bypass Voltage 208V WYE
Nominal Current 251A 109A 87A
Max. Current 350A 150A 125A
Output
Nominal Voltage 208:120V WYE
Frequency 57–63 Hz
Max. Continuous Nominal Current 277.5A
Nominal Current 222A
Wiring
PDU to UPS 4W + G (AC mains input) 4W (Bypass input)
UPS to PDU 4W 4W 4W
PDU to Distribution Panels 4W + G 4W + G 4W + G