American Power Conversion PD80KF6FK1-M Power Supply User Manual


 
Overview
80kW InfraStruXure PDU—Operation and Configuration 11
User connection plate
For a description and location of the user connection plate, see (
) on page 8. For clarity, the user
connection plate is shown in the following illustration in greater detail.
\
Connect the InfraStruXure PDU to the network of the InfraStruXure Manager
through the ethernet port.
The user connection plate has four input contact connections for monitoring
Normally Open (NO) or Normally Closed (NC) dry contacts. See page 20 and
page 64 for more information.
The user connection plate has four relay output connections for connection
of Normally Open (NO) or Normally Closed (NC) dry contacts. See page 20
and page 64 for more information.
Connect an Emergency Power Off (EPO) switch at one of three choices of
EPO connections (24VDC, 24VAC, or contact closure). See page 60 for
more information.
1 234
ATS EN
ATS 0
ATS 1
ATS 2
EPO
Contact
+
EPO 24V
AC/DC
Contact Inputs
Contact Outputs
USER INTERFACE
© 2001 APC
MADE IN USA
!
!
!