American Power Conversion PD80KF6FK1-M Power Supply User Manual


 
Specifications
68 80kW InfraStruXure PDU—Operation and Configuration
Power Cables to Enclosures/ Rack PDUs 4W + G 4W + G 4W + G
Power Cable Connections L21-20 L21-20 L21-20
Power Cable Lengths Various Various Various
Power Cable Wiring (Top Exit) Accommodates 10 + cables
Power Cable Wiring (Bottom Exit) Accommodates 10 + cables
Subfeed
Subfeed Wiring (3 -phase) 4W + G 4W + G 4W + G
Subfeed Connector System 100A, pin and sleeve
Subfeed Voltage 208:120V 208:120V 208:120V
Subfeed Current 80A 80A 80A
Panels
Panel Style
3-phase 3-phase 3-phase
Number of Panels (per PDU) 1 maximum 1 maximum 1 maximum
Positions per Panel 42 42 42
3-phase Breakers per Panel 10 (with 4 subfeeds)
3-phase Subfeeds per Panel 4 maximum 4 maximum 4 maximum
1-phase Breakers per Panel 30 (with 4 subfeeds)
Panel Rating 240V/400A per phase
Panel Board Accessibility Through rear of unit
Relay Outputs
Nominal Switching Capacity 1A at 30VDC
Maximum Switching Power 30W
Maximum Switching Voltage 60VDC
Maximum Switching Current 2ADC
Maximum Carrying Current 2ADC
Surge Ratings 2kV per Bellcore TA-NWT-001089
1.5kV per FCC part 68
Physical PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M
Dimensions (H × W × D)
PDU 81 × 29 × 36 in (2057 × 737 × 914 mm)
AC Power Trough 7.5 × 4.0 × 29.0 in (190 ×100 × 740 mm)
Ramp (L × W) 45 × 6 in (1143 × 150 mm)
Weight
PDU with a Transformer 2100 lb (953 kg)
PDU without a Transformer 1284 lb (583 kg)
Electrical PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M