American Power Conversion PD80KF6FK1-M Power Supply User Manual


 
80kW InfraStruXure PDU—Operation and Configuration 63
How to Connect User Input Contacts and
Relay Outputs to the PDU User Connection
Plate
Overview
Make contact closure connections
(NO or NC) at the user connection
plate to monitor dry contacts. You can
make eight connections—four input
contacts and four relay outputs.
The figure at the right shows the
location of the user connection plate
on the roof of the PDU enclosure.
You can make connections from
inside the enclosure, or you can
remove the user connection plate and
make your connections.
Remove the plate using a Phillips or
standard screwdriver to loosen the
two captive screws. Use the knockout
in the plate to route cables to and from
the user connection plate. If you
remove the plate, make sure that you
do not disturb the existing
connections.
1 234
ATS E N
ATS 0
ATS 1
ATS 2
EPO
Contact
– +
EPO 24 V
AC/D C
Contact Inputs
Contact Outp uts
USER INTERFACE
© 2001 APC