American Power Conversion PD80KF6FK1-M Power Supply User Manual


 
80kW InfraStruXure PDU—Operation and Configuration 13
PDU Display Interface
Overview
You can use the display interface to configure settings, set alarm thresholds, and provide audible and
visual alarms.
ESC
?
Load
Powered
Check
Log
Bypass
Alarm

Load On LED When green, all output phases are within the limits
specified by the output alarm limit thresholds.
Check Log LED When yellow, at least one new alarm condition has been
detected.
Bypass LED When yellow, power to the load is being supplied directly
by the utility power source—the UPS has been removed
from the circuit for maintenance or replacement. Bypass
breakers on the PDU function as input breakers to protect
the load equipment.
Alarm LED When red, an alarm condition exists.
LCD View alarms, status data, instructional help, and
configuration items.
Up and Down
navigation keys
Selects menu items and accesses information.
ENTER key Opens menu items and inputs changes to system
parameters.
HELP key Launches context-sensitive help. Press the HELP key for
information about each item on the screen and for
instructions on how to perform certain tasks (i.e. placing
the UPS into Maintenance Bypass operation).
ESC key Returns to previous screen displayed.