American Power Conversion XS 450 -48 Power Supply User Manual


 
Magnum XS 450 Power System –48 VDC User’s Manual Page 32
3. Verify that the system voltage is above the float voltage if the battery temperature is
below 25 degrees C and below the float voltage if the battery temperature is above 25
degrees C.
4.3 Final Inspection:
1. Verify that the interior and exterior of the system is clean and free from debris.
2. Ensure all wires connected and bolts are properly tightened.
3. Ensure the following the User, Service, and Calibration parameters are set properly on
the controller (default settings are in parenthesis):
LVD
LVD1 Trip
LVD1 Reset
Batt
Batt Disc Thr
Batt Float
Batt Max Rech
Comp Method
4. Verify that the system is functioning correctly with no alarms.
5. Be sure to leave the site as orderly and neat as possible.