American Power Conversion XS 450 -48 Power Supply User Manual


 
Magnum XS 450 Power System –48 VDC User’s Manual Page 39
Battery Preventive Maintenance Procedure
The purpose of the preventive maintenance is to ensure that the battery is in good, working
condition. The observations, measurements, and tests performed are designed to determine
the “state of health” of the battery. It will also allow for the prediction of future performance
and preempt possible failure.
1. Measure the float charge voltage.
a. At the power bay bus.
b. At the battery.
c. Reset voltage if necessary.
2. Measure the float current on each battery cable. If it is fluctuating, measure
maximum and minimum.
3. Measure the ac ripple voltage at the battery.
4. Measure and record the float voltage of each cell or monoblock.
5. Perform a load test on each cell or monoblock and measure the internal cell
resistance and inter-cell resistance of each cell or monoblock.
6. Ensure that all protective covers are replaced and that the battery is electrically non-
hazardous to personnel that could be working in the vicinity
6.4 Final Inspection:
1. Verify that the interior and exterior of the system is clean and free from
debris.
2. Ensure all wires connected and bolts are properly tightened.
3. Ensure the following the User, Service, and Calibration parameters are set
properly on the controller (default settings are in parenthesis):
LVD
(Param)
LVD1 Trip (-42.00 V)
LVD1 Reset (-48.00 V)
Batt
(Set-alm)
Batt Disc Thr (10 A)
Batt
(Param)
Batt Float (-54.00 V)
Batt Max Rech (10 A)
Batt
(Comp)
Comp Method (ON).
4. Verify on the status menu that the system is functioning correctly with no
alarms.
5. Be sure to leave the site as orderly and neat as possible.