Emerson Process Management 3-9000-522 Whiteboard Accessories User Manual


 
5-50 APPLICATION FUNCTIONS
MON2000
Analog Output Dialog Description JULY 2010
See the following table for details.
Table 5-9 Description of Analog Output Settings
Setting Description
<Number> number assigned to Analog Output
Number of available analog outputs is
dependent upon the GC Controller model.
Variable type of GC analysis data on which to base
signal level of analog output
Stream stream number assigned to the variable or
the channel number if referencing an
analog output
Component name of component monitored by this
output
Current Value current readout values of the analog output
(values reflect scale assignments)
Zero Scale value used to represent the minimum value
(4mA) when scaling the analog output
value
Full Scale value used to represent the maximum
value (20mA) when scaling the analog
output value
Fixed/Var analog output operation mode
Fixed = fixed
Var = variable
If the operation mode is fixed, the analog
output is set to the number entered for the
Fixed Value.
If the GC unit includes a Daniel Analog
Expansion Module (AEM), P/N 1-0500-
001, reserve analog output number 1
(first row) for the variable Bargraph.