4. Troubleshooting (DeviceNet)
Status Code
General Protocol
Descriptions
45 Non-resident dialogue software.
Additional information:
Initialize the applicomIO® interface before use by
running the PcInitIO
47 Targeted applicomIO® card invalid or incorrectly
initialized by the function IO_Init
53 Synchronization problem on the line.
Additional information:
The DeviceNet master is "off line" (power supply
not detected or the CAN component of the
applicomIO® is "Bus Off")
Check the network wiring and Baud Rate.
55 Response time-out exceeded.
Additional information:
The device accepted the connection but did not
answer the request.
Check the device status.
65 Connection denied.
Additional information:
Connection to the DeviceNet master is in progress
or refused by the device.
70 Connection finished.
Additional information:
Duplication of MAC ID detected on the DeviceNet
network.
Modify the MAC ID of the DeviceNet master.
79 Profile incompatible.
Additional information:
The device does not match the configuration.
Check the device identity and the connection sizes.
63 Indicates that a communication error has been
encountered on serial Port.
66 Not enough applicomIO® interface memory.
93 Driver cannot be accessed.
99 Indicates that applicomIO® solution is already
running.
255 Indicates that the local input buffer was not updated
beforehand by the function IO_RefreshInput.
Fieldbus I/O Rev.6 109