General Specifications
Electrical Specifications
Item Specification
Supply Voltage 5 V DC (supplied from a controller)
Power Consumption 5.5 W
Ambient Temperature during Operation 5-40 deg C
Relative Humidity during Operation 20-80%
PROFIBUS DP Communication Specifications
Item Specification
Connection Method Hybrid
(token passing procedure and master-slave communication)
Baud Rates 9.6 kbps, 19.2 kbps, 93.75 kbps, 187.5 kbps, 500 kbps,
1500 kbps, 3 Mbps, 6 Mbps, and 12 Mbps.
Baud Rates Cable Length Transfer Distance
12 Mbps
6 Mbps
3 Mbps
1500 kbps
500 kbps
187.5 kbps
93.75 kbps
19.2 kbps
9.6 kbps
100 m
100 m
100 m
200 m
400 m
1000 m
1200 m
1200 m
1200 m
Maximum Stations 126 (including master unit and repeater)
Data Length / Frame 244 bytes
Cable 2-wire cable dedicated to PROFIBUS (2 wires for signal)