Epson EM07ZS1647F Network Card User Manual


 
4. Troubleshooting (PROFIBUS DP)
Causes of Error
Possible Cause Examination Method Countermeasure
{ Disconnected
terminating resistors
{ Cable disconnection
{ Disconnected
connector
{ Disconnected signal
wire
(1) Check that terminating
resistors are connected to
both ends of the network.
(2) Measure resistance between
signal wires with device
power supply OFF.
Normal: 100 to 120
z Measuring point: Connection
of the trouble unit
z For detail, refer to the section
4.2.3.1 Connection Problem.
Fix the problem.
How to find the trouble
point:
Remove the terminating
resistor on one end of the
network. The trouble point
is where resistance
changes from 220
.
{ Loose connector
{ Loose signal wire
Check for the connection of
connectors and signal wires.
The connectors and signal
wires should be firmly
connected.
z Checkpoint: all stations and all
branch taps
z For details, refer to the section
4.2.3.2 Loose Connector and
Signal Wire.
Connect the connectors
and signal wires again.
{ Noise
(external cause)
Check the noise intrusion via the
following paths (1) to (3).
(1) Noise via shield
(2) Induced noise via
communication cable
(3) Device power supply
For details, refer to the section
4.2.3.3 Noise Intrusion.
Take countermeasures
against noise.
{ Broken unit Replace the trouble unit with a
new one.
Verify whether the problem is
fixed.
Replace the unit with a
new one.
z No cause is
identified.
Identify the trouble point by
dividing the network.
For details, refer to the section
4.2.3.4 Broken Unit
Examination.
Fieldbus I/O Rev.6 125