GE LTC MAP Computer Monitor User Manual


 
70055MP Revision D February 3, 2000
Section 3: Installation
This Section includes procedures for installation, configuration, wiring,
setting up communications, and initial start-up of the LTC-MAP 2130
Monitor.
Selecting a Location
The LTC-MAP 2130 is enclosed in a weatherproof stainless steel box that
can be mounted indoors or outdoors. When selecting a mounting location
for the monitor, verify that:
The mounting surface is able to support a minimum of 25 pounds (11.3
kg).
The mounting surface allows ample space for mounting the stainless
steel box and allows for a 12-inch (305 mm) door clearance (see Figure
3-1).
Sensors are located nearby to minimize cable length.
Wiring and cables can access the monitor gland plate.
The face panel display is at a readable level.
An operating temperature of 0 ºC to +60 ºC (+32 ºF to +140 ºF) can be
maintained at the monitor location.
NOTE: With the heater option installed, an operating temperature of
-40 ºC to +º60 C (-40 ºF to +140 ºF) must be maintained at the
monitor location.
CAUTION: Select a mounting location that assures an operating
temperature of 0 ºC to +60 ºC (+32 ºF to +140 ºF), otherwise system operation
could be interrupted.