ENI Configuration (Node 248 to 254) 4-11
Node 248 - Save/Reset Function
Depending on the value of the Save/Reset option, the ENI performs
the following operations when receiving a PCCC Unprotected Write
message of one element (integer) to Node 248.
Node 249 - From String
Node 249 holds the ASCII string that is sent with any e-mail message
initiated by the ENI. Criteria for a valid E-mail From String include:
• The From String remains at the default value unless changed by
the user. See page 4-10 for default information.
• The From String must contain an “@” symbol.
• The From String cannot contain any spaces or special ASCII
characters.
• The maximum length of the From String is 64 characters. Any
additional characters are ignored.
• The From String is sent from a String Table consisting of 84
characters.
• To configure the From String, initiate a message with a string
element as the data. The message instruction procedure is
shown on page 4-8.
Value of
Save/Reset
ENI Operation
0 The ENI immediately stops all normal operations and saves the
configuration to non-volatile memory.
IMPORTANT
The ENI may take up to 60 seconds to complete
this save operation. The configuration is not
permanently saved until the Save command is
sent.
1 The ENI immediately stops all normal operations and performs a soft
reset.
2 The ENI immediately stops all normal operations, performs a soft
reset, and returns all parameters to their “out-of-box” settings.
3 The ENI immediately stops all normal operations, performs a soft
reset, and returns all parameters to their “out-of-box” settings (except
for the IP address, Subnet Mask, Gateway ID, and Security Mask).