Particulate contamination
Attention: Airborne particulates (including metal akes or particles) and reactive gases acting alone or in
combination with other environmental factors such as humidity or temperature might pose a risk to the
server that is described in this document. Risks that are posed by the presence of excessive particulate
levels or concentrations of harmful gases include damage that might cause the server to malfunction or
cease functioning altogether. This specication sets forth limits for particulates and gases that are intended
to avoid such damage. The limits must not be viewed or used as denitive limits, because numerous
other factors, such as temperature or moisture content of the air, can inuence the impact of particulates
or environmental corrosives and gaseous contaminant transfer. In the absence of specic limits that are
set forth in this document, you must implement practices that maintain particulate and gas levels that are
consistent with the protection of human health and safety. If Lenovo determines that the levels of particulates
or gases in your environment have caused damage to the server, Lenovo may condition provision of repair
or replacement of servers or parts on implementation of appropriate remedial measures to mitigate such
environmental contamination. Implementation of such remedial measures is a customer responsibility.
Table 5. Limits for particulates and gases
Contaminant Limits
Particulate
The room air must be continuously ltered with 40% atmospheric dust spot efciency
(MERV 9) according to ASHRAE Standard 52.2
1
.
Air that enters a data center must be ltered to 99.97% efciency or greater, using
high-efciency particulate air (HEPA) lters that meet MIL-STD-282.
The deliquescent relative humidity of the particulate contamination must be more than 60%
2
.
The room must be free of conductive contamination such as zinc whiskers.
Gaseous Copper: Class G1 as per ANSI/ISA 71.04-1985
3
Silver: Corrosion rate of less than 300 Å in 30 days
1
ASHRAE 52.2-2008 - Method of Testing General Ventilation Air-Cleaning Devices for Removal Efciency by Particle
Size. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
2
The deliquescent relative humidity of particulate contamination is the relative humidity at which the dust absorbs
enough water to become wet and promote ionic conduction.
3
ANSI/ISA-71.04-1985. Environmental conditions for process measurement and control systems: Airborne
contaminants. Instrument Society of America, Research Triangle Park, North Carolina, U.S.A.
Important WEEE information
The WEEE marking on Lenovo products applies to countries with WEEE and e-waste regulations (for example,
European Directive 2002/96/EC, India E-Waste Management & Handling Rules, 2011). Appliances are
labeled in accordance with local regulations concerning waste electrical and electronic equipment (WEEE).
These regulations determine the framework for the return and recycling of used appliances as applicable
172 ThinkServer RD540 User Guide and Hardware Maintenance Manual