MGE UPS Systems 3.5 to 21 kVA N+1 Power Supply User Manual


 
Introduction
page 1 — 3
Owner’s Manual
Table 1-2: Inverter Module Dimensions.
Inverter Module HEIGHT (in/cm) DEPTH (in/cm) WIDTH (in/cm) WEIGHT (lb/kg)
64004-9MSK1 5.18 / 13.16 15.12 / 38.4 15.76 / 40.03 46 / 20.86
Note: Weight: Six-mod receiver = 135 lbs. (61.2 kg) 1 UPS Module = 46 lbs. (20.09 kg)
Total System Weight, 21 kVA system = 411 lbs. (186.4 kg)
1.3 Electrical Specifications
Electrical Specifications are subject to revision without notice.
1.3.1 DC Input
Nominal: -48Vdc; Operating Range: -39.5Vdc to -57 Vdc
NOTE: An external DC circuit breaker or fuse should be used at the DC
source.
1.3.2 AC Output (per module)
Voltage: 120Vrms or 240Vrms
Current: 25Arms or 12.5Arms
Frequency: 60Hz or 50Hz
Table 1-3: S4 AC Output Current Ratings.
Attention: Watts rating = 85% of the VA rating at 120/240 VAC.
MAXIMUM OUTPUT RATINGS
7 KVA unit 14 KVA unit 21 KVA unit
Vout Iout Output Output Iout Output Output Iout Output Output
(Vac) (A) Power VA (A) Power VA (A) Power VA
(W) (VA) (W) (VA) (W) (VA)
110 58.33 6000 6416 116.66 12000 12833 175 18000 19250
115 58.33 6000 6708 116.66 12000 13416 175 18000 20125
120 58.33 6000 7000 116.66 12000 14000 175 18000 21000
208 29.165 6000 6066 58.33 12000 12133 87.5 18000 18200
220 29.165 6000 6416 58.33 12000 12833 87.5 18000 19250
230 29.165 6000 6708 58.33 12000 13416 87.5 18000 20125
240 29.165 6000 7000 58.33 12000 14000 87.5 18000 21000
Units configured to other then 120/240VAC are derated due to current limit.
The % Load reading on the display panel is always with reference to the 120/240 Vac WATT and VA ratings.