MGE UPS Systems 3.5 to 21 kVA N+1 Power Supply User Manual


 
Installation & Operation - Line To Line
page 2 — 15
Owner’s Manual
Figure 2-7: Line To Line Setup Screen.
After the selections are complete, click on the Save button. The data will be sent to the appropriate address in the
controllers “EEROM”. Remove the applied 48VDC to the system by turning off the main DC feed circuit breaker.
2.9.3 Unit kVA Rating ID Label
For kVA rating see the inverter ID label. Use the label kVA rating, regardless of the number of inverter modules
installed.
The processor will detect and display the number of modules installed and the number of modules that are “ON”
and operating without fault. MGE is offering the 7, 14, and 21 kVA rating.
2.9.4 On-Line Mode
On-line mode is the mode in which the load is powered by the inverter system, not the utility. It will get clean, tran-
sient free electrical power from the inverter system, which is producing the AC power from a DC power source. In
the event of inverter failure, the static transfer switch will transfer the load to the utility power if available.
2.9.5 Off-Line Mode
Off-line mode is the mode in which the load is powered from the Utility power line (external AC input power). In the
event of a power failure, a static transfer switch will connect the system output to the inverter and activate the invert-
er so as to provide continuous power to the load with no interruptions of power to the load.
x
?
Line To Line Inverter Configuration
Rack kVA rating
Utility
Inverter voltage
Mode
Inverter frequency
DC fail auto restart
Cancel
Save
7.0 14.0 21.0
Voltage connected
AC tree
On-line
Off-line
208 220 230 240
50 hz 60 hz