Mitsumi electronic NZ2GF-ETB Network Card User Manual


 
106
7.3.1 Deciding the IP address
This section explains how to set an IP address to perform communications over CC-Link IE Field Network.
(1) When the network addresses of the request source external device, request
destination external device, and modules between them are the same
Communications can be performed with the minimum setting by setting the same network address of the IP
address in the request source external device, request destination external device, and modules between them.
The IP addresses of the request source external device, request destination external device, and modules
between them must meet the rules below. Especially, pay attention to the setting ranges of the third and fourth
octets.
*1 Set the numbers according to the range supported by the external device used.
The range may not apply depending on the external device. Check the specifications of the external device used.
To transmit communications to the external device, the routing parameters are required. ( Page 109, Section 7.3.4 (1))
Device to be set
Setting range of the IP address
First and second octets Third octet Fourth octet
External device
0.0 to 223.255
*1
(Same numbers for the request
source external device, request
destination external device, and
modules between them)
1 to 239
*1
(Same number for the external
device and the Ethernet adapter
module (Ethernet part) connected
to the external device)
1 to 120
*1
Ethernet adapter module (Ethernet
part)
Ethernet adapter module (CC-Link
IE Field Network part)
Automatically set (network
address of the master station)
0.0 to 223.255
*1
Automatically set (network number
of the own station)
1 to 239
Automatically set (station
number of the own station)
• 1 to 120
Master/local module
0.0 to 223.255
*1
(Same numbers for the request
source external device, request
destination external device, and
modules between them)
Automatically set (station
number of the own station)
• 1 to 120
• 125 (125 is always set in the
master station)
CPU module connected to the
external device
0.0 to 223.255
*1
(Same numbers for the request
source external device, request
destination external device, and
modules between them)
1 to 239
*1
(Same number for the external
device and the CPU module)
1 to 120
*1
Universal model QCPU on the
communication route (not
connected to the external device)
IP address setting not required
192 . 168 . 10 . 36
Network address
Setting range: 0.0 to 223.255
Use the same numbers for the networks of the request
source external device, request destination external device,
and modules between them.
Setting range: 1 to 239
and
a value not used for other network modules and other
CPU modules using the IP packet transfer function
Setting range: 1 to 120