Mitsumi electronic NZ2GF-ETB Network Card User Manual


 
191
CHAPTER 10 CONFIGURATION TOOL
10
10.3 Parameters
10.3.3 Ethernet setting
(1) Connection Setting
Configure the Ethernet Connection settings. Up to 32 Connections can be set.
Setting item tree NZ2GF-ETB [Parameter] "Ethernet" button
The following table lists the setting items on the window.
If the button is clicked on the "Ethernet Port Connection Setting" window, the parameters set in the "Detail Setting"
dialog box are also set to default values.
Item Description Setting range
MELSOFT
Select the checkbox when using the connection for MELSOFT connection.
When the checkbox is selected, items after "Connection Data Code" are
automatically set.
Selected/Not selected
(Default: Not selected)
Communication Data Code Set a communication data code.
Binary Code/ASCII Code
(Default: Binary Code)
Protocol Set a communication protocol.
TCP/UDP
(Default: TCP)
Own Station Port No.
Set the Own Station Port No. Set a unique number for each Connection. If
Connection is selected to be used for MELSOFT in "MELSOFT", "MELSOFT
Connection" is displayed for the connection.
• Decimal input
1025 to 4999, 5011 to 65534
H
(Default: 8192 to 8223)
• Hexadecimal input
0401
H
to 1387, 1393
H
to FFFE
H
(Default: 2000
H
to 201F
H
)
Detail Setting
Set the Connection details. (
Page 192, Section 10.3.3 (1) (a))
Port No. Input Format Select a port number input format.
HEX/DEC
(Default: HEX)