CHAPTER 7 COMMUNICATION OF THE ETHERNET ADAPTER MODULE
7
7.3 IP Communications over CC-Link IE Field Network (IP Packet Transfer Function)
7.3.4 Connection to CC-Link IE Field Network
7.3.4 Connection to CC-Link IE Field Network
Set the parameters in the master station for IP communications over CC-Link IE Field Network.
(1) Setting in the master station
Use GX Works2 to set the parameters in the master station. Use the default settings for the parameters other than
those set below.
1. Create a project on GX Works2.
[Project] [New...]
2. Open the "Network Parameter" setting window to set the parameters as follows.
Project window [Parameter] [Network Parameter] [Ethernet/CC IE/MELSECNET]
Setting