50 CallPilot
DC wire gauge tables
Introduction
The tables in this section specify the DC power feed wire requirements.
Cabinet and module DC feed recommended wire gauge
specifications
Notes:
1. The cabinet and module ground wire specification is #10 AWG insulated
green safety ground wire.
2. The cabinet conduit can be 19.1 mm (0.75-in.) or 31.8 mm (1.25-in.),
and must be insulated from the cabinet ground.
Length #10 AWG #8 AWG #6 AWG
Junction
box #4
AWG
Junction
box #4
AWG
0–30 m (100 ft) yes yes yes yes yes
0–45 m (150 ft) no yes yes yes yes
0–75 m (250 ft) no no yes yes yes
0–135 m (450 ft) no no no yes yes
0210 m (700 ft)nonononoyes
Over 210 m (700 ft)nonononono