42 Chapter 2 Nortel VPN Router 1750 chassis
NN46110-316 03.01
Installing the chassis in an equipment rack
To mount the VPN Router 1750 in an equipment rack, you need the following
equipment:
standard 19-inch equipment rack
four screws (supplied with the chassis)
four cage nuts (supplied with the chassis) if the rack does not have threaded
rail holes
a #2 Phillips screwdriver
Rack-mount recommendations
When you mount the chassis in the equipment rack, observe the following
standard recommendations:
The maximum recommended ambient temperature is 40
o
C (104
o
F). Ensure
that the internal temperature of the rack does not exceed 40
o
C (104
o
F).
Do not block the power supply vents or otherwise restrict air flow when you
install the chassis in the rack.
Stabilize the rack so that it does not tip over under the weight of the gateway
and other devices.
Before you install and turn on the gateway, ensure that the electrical branch
circuits can handle the VPN Router 1750 and other units in the rack.
Maintain a reliable earth-ground path in the rack system. You must connect
the gateway to an earth ground.
Attaching the shelf in the equipment rack
The VPN Router 1750 ships with a rack-mount shelf to support the chassis in the
equipment rack.
To attach the shelf to the inside of the equipment rack, perform the following
steps: