238
Remote Programming and Monitoring Section 7-2
CX-Programmer
A CX-Programmer connected to a CS/CJ-series, C200HX/HG/HE, CVM1,
CV-series, or CQM1H-series CPU Unit can program and monitor any other
PLC on another Controller Link Network. Other types of PLC, different to the
one to which the CX-Programmer is connected can also be programmed or
monitored on remote networks.
Note 1. Version 1.20 of CX-Programmer must be used for the CQM1H-series Con-
troller Link Unit.
2. Use CX-Programmer version 2.04 or higher for a CJ-series Controller Link
Unit.
7-2-3 Other Remote Networks
SYSMAC Support Software or CV Support Software
A Programming Device connected to a CVM1 or CV-series CPU Unit can pro-
gram and monitor a CVM1 or CV-series PLC on a different type of network
(SYSMAC NET or SYSMAC LINK) through a CVM1 or CV-series PLC. Other
types of PLC cannot be programmed or monitored on remote networks.
Note Remote
p
ro
g
rammin
g
and monitorin
g
is
p
ossible from com
p
uter nodes.
Controller Link Network Controller Link Network
CX-Programmer
Programming Device
Controller Link Network Controller Link Network
Programming
and monitoring
CS/CJ-series, C200HX/HG/
HE, CVM1, CV-series, or
CQM1H-series PLC
Controller Link
Support Software
CS/CJ-series,
CVM1, or CV-
series PLC
CX-Programmer
CS1-series PLC
CVM1 or
CV-series PLC
CS/CJ-series, C200HX/HG/
HE, CVM1, CV-series, or
CQM1H-series PLC
Controller Link Network
Controller Link Network Controller Link Network
SYSMAC Support
Software (CVM1 Only)
or
CV Support Software
Programming Device
Programming
and monitorin
g
CVM1 or CV-series PLC
CVM1 or CV-series PLC
CVM1 or CV-series PLC
Controller Link
Support Software
CVM1 or CV-
series PLC
SYSMAC NET
Remote programming and monitoring is not possible from computer nodes.
Computer nodes can only monitor Controller Link Network status.
A Programming Device connected to a C200HX/HG/HE PLC cannot remotely
p
ro
g
ram or monitor a node on a remote network.
Note