Omron C200HW-CLK21 Network Card User Manual


 
26
Basic Procedures Section 1-4
other PLCs in other nodes or from one PLC to IBM PC/AT or compatible com-
puters.
1-4 Basic Procedures
Preparations C200HX/HG/HE and CQM1H-series PLCs
1,2,3... 1. Perform mounting and wiring.
Mount to the PLC.
Connect the communications cables.
2. Set the node address on the front rotary switches.
01 to 32
3. Set the baud rate and operating level on the front DIP switch.
2 M, 1 M, or 500 Kbps
Operating level 0 or operating level 1 (C200HX/HG/HE PLCs only)
4. Set the terminating resistance on the sliding switch.
ON or OFF (Only the end nodes are set to ON.)
5. Connect power to all nodes.
6. Connect the Programming Device to the PLC.
7. Create I/O tables (not necessary for C200HX/HG/HE and CQM1H-
series PLCs and not necessary for CJ-series PLCs unless user-created
I/O tables have been specified).
8. Register routing tables as required.
CVM1, CV-series, and CS/CJ-series PLCs
1,2,3... 1. Perform mounting and wiring.
Mount to the PLC.
Connect the communications cables.
2. Set the Unit number on the front rotary switches.
00 to 15 (0 to F: CS/CJ-series display is in hexadecimal)
3. Set the node address on the front rotary switches.
01 to 32 (01 to 62) (See note a.)
4. Set the baud rate and operating level on the front DIP switch.
2 M, 1 M, or 500 Kbps (wired systems only)
5. Set the terminating resistance on the front slide switch.
ON or OFF (Only the terminal node is set to ON.)
6. Connect power to all nodes.
7. Connect the Programming Device to the PLC.
8. Create I/O tables (not necessary for C200HX/HG/HE and CQM1H-
series PLCs and not necessary for CJ-series PLCs unless user-created I/
O tables have been specified).
9.
Set the Wired Network 62 Node Enable Bit in the DM Parameter Area soft-
ware switches. (See note b.)
ON (62 nodes max.) or OFF (32 nodes max.)
10. Register routing tables.
Note a) Setting 62 nodes is possible only with the CS1W-CLK21-V1 and
CJ1W-CLK21-V1.
The Wired Network 62 Node Enable Bit in the
DM Parameter Area software switches must be set.