317
Error Log Section 9-3
0109
Hex
Transmission failed; destination
busy
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Increase number of
retries or reconfig-
ure system to distrib-
ute load.
No All
010A
Hex
Transmission failed; communica-
tions controller error
Conduct an echo-
back test and if the
effects of noise are
considerable, recon-
sider the operating
environment. Restart
the Controller Link
Unit. If the error
occurs again,
replace the Unit.
Ye s A l l
010B
Hex
Transmission failed; PLC error Refer to the PLC
operating manual. If
the error occurs
again, replace the
PLC.
No All
010C
Hex
Transmission failed; unit number
incorrect
Check unit number
settings to be sure
they are within range
and unique.
No CV, CS/CJ
010D
Hex
Transmission failed; destination
address incorrect
Check routing tables. No All
010E
Hex
Transmission failed; routing
tables not registered
Check routing tables No All
010F
Hex
Transmission failed; routing table
error
Check routing tables. No All
0110
Hex
Transmission failed; too many
relay points
Check routing tables
and system configu-
ration. Use a CS/CJ-
series CPU Unit with
unit version 2.0 or
later and CX-Pro-
grammer Ver. 4.0 or
higher to send com-
mands across three
or more network lev-
els.
No All
0111
Hex
Transmission failed; command
packet too long
Be sure to use the
FINS command
format.
No All
0112
Hex
Transmission failed; header
error.
Be sure to use the
correct FINS
command format.
No All
0113
Hex
Transmission failed; I/O setting
error
Check I/O table
accuracy.
No CV, CS/CJ
0114
Hex
Transmission failed; CPU bus
error
Check Unit and cable
connections and
clear error.
No CV, CS/CJ
0115
Hex
Transmission failed; redundant I/
O allocations
Check unit numbers
for redundancy within
the same PLC.
No CV, CS/CJ
0116
Hex
Transmission failed; CPU Bus
Unit error
Check Unit and cable
connections and
clear error.
No CV, CS/CJ
Error
code
Contents Detail code Correction Written to
EEPROM
Applicable
PLC
1st byte 2nd byte