Omron C200HW-CLK21 Network Card User Manual


 
315
Error Log Section 9-3
000E
Hex
I/O Bus error 00 Hex 00 Hex Check the operating
environment.
Ye s C S / C J
000F
Hex
PLC initialization error Check the operating
environment.
Ye s C S / C J
0010
Hex
PLC Setup exceeds capacity Reduce the number
of CPU Bus Units
mounted on each
CPU Unit by one.
Ye s C S / C J
0011
Hex
PLC initialization error
(Time out)
Check the operating
environment.
Ye s C S / C J
0012
Hex
CPU Unit memory error 01 Hex:
Read error
02 Hex:
Write error
01 Hex:
Data link
table
02 Hex: Net-
work param-
eters
03 Hex:
Routing
table
04 Hex: PLC
Setup Area
Reset the appropri-
ate data.
Ye s C S / C J
0013
Hex
CPU Unit write-protected Release the CPU
Unit write protect.
Ye s C S / C J
Error
code
Contents Detail code Correction Written to
EEPROM
Applicable
PLC
1st byte 2nd byte