12--12
Powerware 9330 (10 kV A--40 kVA) Installation and Operation
164201300 REV. G 061502
12.5.2 Event History Log
This key sequence prints the entire Event History Log of the UPS at the time the
data is requested. The printout begins with the oldest alarm entry in the queue and
ends with the most recent. Any alarms that occur while the Event History Log is
printing are included in chronological order.
The Event History Log lists up to 500 system events in chronological order with the
most recent event listed last. Figure 12---18 shows a sample Event History Log
printout.
In this mode, system events are continually logged through the serial port to the
device connected to the port.
The printed log entries contain a time and date stamp and the alarm text message.
Terminal mode uses this format for printing alarm entries:
MM DD YYYY HH:MM:SS.hh KYWD MESSAGE :::: <CR> <LF>
Symbol Description
MM Month (2 digits)
YYYY Year (4 digits)
DD Day (2 digits)
HH Hour (2 digits)
MM Minute (2 digits)
SS Second (2 digits)
hh Hundredths of Second (2 digits)
KYWD Keyword (ALARM, NOTICE , COMMAND, or STATUS)
:::: System Diagnostic Information
<CR> Carriage Return Character (ASCII 13)
<LF> Line Feed (ASCII 10)
An alarm message is prefixed by the word “CLEAR” whenever an alarm is entered
into the Event History L og with a cleared status.
If a port is operating in Terminal mode and is connected to a computer, you can
use key combinations at any time to print selected information:
Esc+H Prints the entire log with a firmware version header
To use a key combination, hold down the Esc key and press the letter key.