DESCRIPTION:
DATE:
DRAWING NO:
1of2
SHEET:
REVISION:
G
061502
PHYSICAL FEATURES AND REQUIREMENTS
164201300---3
A --- 2 4
Powerware 9330 (10 kV A--40 kVA) Installation and Operation
164201300 REV. G 061502
1. The UPS equipment operating environment must meet the size and weight requirements
shown in Table AA, according to your UPS system configuration.
2. In the UPS system, the U PS, Options, and Battery cabinets are palleted separately for
shipping.
3. Donottiltcabinetsmorethan10˚ during handling.
4. Dimensions are in millimeters (inches).
T
a
b
l
e
A
A
E
q
u
i
p
m
e
n
t
W
e
i
g
h
t
Table AA. Equipment Weight
C
o
m
p
o
n
e
n
t
Weight
Kg (lb)
C
o
m
p
o
n
e
n
t
Shipping Installed Point Loading
UPS Cabinet with Filter and Batteries
Powerware 9330 (10 kVA---20 kVA)
461 (1017) 435 (958) 6 at 73 (160)
UPS Cabinet with Filter and Batteries
Powerware 9330 (25 kVA---40 kVA)
873 (1925) 838 (1847) 9 at 93 ( 205)
Options Cabinet with PDM and no transformer
Powerware 9330 (10 kVA---20 kVA)
118 (260) 90 (200) 4at23(50)
Options Cabinet with PDM and 1 transformer
Powerware 9330 (10 kVA---20 kVA)
240 (530) 213 (470) 4 at 53 (118)
Options Cabinet with PDM and 2 transformers
Powerware 9330 (10 kVA---20 kVA)
358 (790) 331 (730) 4 at 83 (183)
Options Cabinet with PDM and no transformer
Powerware 9330 (25 kVA---40 kVA)
154 (340) 120 (265) 6at20(44)
Options Cabinet with PDM and 1 transformer
Powerware 9330 (25 kVA---40 kVA)
471 (1040) 437 (965) 6 at 73 (161)
Options Cabinet with PDM and 2 transformers
Powerware 9330 (25 kVA---40 kVA)
782 (1725) 748 (1650) 6 at 125 (275)
Battery Cabinet 361 (795) 333 (735) 6 at 56 (123)
NOTES:
Powerware 9330 (10 kVA---20 kVA)
1. For UPS Cabinet without Filter, subtract 25 Kg (55 lb).
2. For UPS Cabinet without Batteries, subtract 227 Kg (499 lb)
3. For Options Cabinet without PDM, subtract 11 Kg (25 lb)
Powerware 9330 (25 kVA---40 kVA)
1. For UPS Cabinet without Filter, subtract 41 Kg (90 lb).
2. For UPS Cabinet without Batteries, subtract 453 Kg (998 lb)
3. For Options Cabinet without PDM, subtract 11 Kg (25 lb)
5. TheclearancesrequiredaroundtheUPSSystemareshowninTableAB.
Table AB. System Clearances
From Front of Cabinet 36 inches working space
From Back of Cabinet 12 inches air circulation clearance
From Sides of Cabinet Allow space for Options and Battery Cabinets