Powerware 9330 Power Supply User Manual


 
14--2
Powerware 9330 (10 kV A--40 kVA) Installation and Operation
164201300 REV. G 061502
Observe these precautions when working on or around batteries:
· Remove watches, rings, or other metal objects.
· Use tools with insulated handles.
· Wear rubber gloves and boots.
· Do not lay tools or metal parts on top of batteries or battery cabinets.
· Disconnect the charging source prior to connecting or disconnecting terminals.
· Determine if the battery is inadvertently grounded. If it is, remove the source of
the ground. Contact with any part of a grounded battery can result in electrical
shock. The likelihood of such shock will be reduced if such grounds are
removed during installation and maintenance.
· When replacing batteries, use the same number of sealed, lead-acid batteries.
· Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
WARNING:
HAZARDOUS WASTE. Do not incinerate or dispose of batteries
indiscriminately. Observe local and national codes.
WARNING:
Do not dispose of battery or batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes, and may be toxic.
A battery can cause electrical shock, burn from high short-circuit current, or
fire. Observe proper precautions.
ATTENTION:
Une batterie peut prêsenter un risque de choc êlectrique, de brulure, ou
d’incendie. Suivre les précautions qui s’imposent.
· Pourleremplacement,utiliserlemêmenombreetmodéledesbatteries.
· L’élimination des batteries est règlementée. Consulter les codes locaux à cet
effet.